Tap changing transformers

Tap changing transformers :

The excitation control method is satisfactory only for relatively short lines. However, it is not suitable for long lines as the voltage at the alternator terminals will have to be varied too much in order that the voltage at the far end of the line may be constant. 

Under such situations, the problem of voltage control can be solved by employing other methods. One important method is to use tap changing transformer and is commonly employed where main transformer is necessary. In this method, a number of tappings are provided on the secondary of the transformer. The voltage drop in the line is supplied by changing the secondary e.m.f. of the transformer through the adjustment of its number.

1. Off load tap changing transformer:

The arrangement where a number of tappings have been provided on the secondary. As the position of the tap is varied, the effective number of secondary turns is varied and hence the output voltage of the secondary can be changed.see fig below:
Off load tap changing transformer
Off load tap changing transformer

When the movable arm makes contact with stud 1, the secondary voltage is minimum and when with stud 5, it is maximum. During the period of light load, the voltage across the primary is not much below the alternator voltage and the movable arm is placed on stud 1. When the load increases, the voltage across the primary drops, but the secondary voltage can be kept at the previous value by placing the movable arm on to a higher stud. Whenever a tapping is to be changed in this type of transformer, the load is kept off and hence the name off load tap changing transformer.

The principal disadvantage of the circuit arrangement. It cannot be used for tap changing on load. Suppose for a moment that tapping is changed from position 1to position 2 when the transformer is supplying load. If contact with stud 1 is broken before contact with stud 2 is made, there is break in the circuit and arcing results. On the other hand, if contact with stud 2 is made before contact with stud 1 is broken, the coil connected between these two tappings are short-circuited and carry damaging heavy current. For this reason, the above circuit arrangement cannot be used for tap changing on load.

2. On-load tap- changing transformer:

In supply system, tap-changing has normally to be performed on load so that there is no interruption to supply. The secondary consists of two equal parallel windings which have similar tappings 1a.......5a and 1b.........5b. In the normal working conditions, switches a, b and tapping with the same number remain closed and each secondary winding carries one-half of the total current. Show the fig below:
On load tap-changing transformer
On load tap-changing transformer

The secondary voltage will be maximum when switches a, b and 5a, 5b are closed. However, the secondary voltage will be minimum when switches a, b and 1a, 1b are closed.

Suppose that the transformer is working with tappings position at 4a, 4b and it is desired to alter its position to 5a, 5b. For this purpose, one of the switches a and b, say a, is opened. This takes the secondary winding controlled by switch a out of the circuit.

Now the secondary winding controlled by switch b carries the total current which is twice its rated capacity. Then the tapping on the disconnected winding is changed to 5a and switch a is closed. After this, switch b is opened to disconnect its winding, tapping position on this winding is changed to 5b and then switch b is closed. In this way tapping position is changed without interrupting the supply. This method has the following disadvantages:
  1. During switching, the impedance of transformer is increased and there will be a voltage surge.
  2. There are twice as many tappings as the voltage steps.